Fire stopping

How to spot damaged fire stopping

New cables, pipework and maintenance activity can disturb compartment lines. Early reporting helps prevent an unrecorded opening from becoming a route for smoke and fire.

5minute guideReviewed for an England-based audience
01

Common warning signs

Damage is not always a large open hole. Small annular gaps, removed collars, unsupported systems or unsealed additions may all need investigation.

  • Unsealed cable or pipe additions
  • Cracked, incomplete or loose sealant
  • Damaged coated batt or missing sections
  • Pipe collars or wraps that are loose, incomplete or absent
  • Openings hidden above ceilings or inside risers
02

Avoid improvised repairs

Generic foam, mortar or sealant is not automatically a fire-stopping system. Suitability depends on the substrate, service, opening, supports and required rating.

  • Do not fill the opening with an unidentified product
  • Photograph the location before touching it
  • Record nearby asset or room references
  • Escalate to a competent passive fire specialist
03

What a proper close-out should show

A useful record links the finished installation to a location and suitable tested detail.

  • Unique location reference
  • Product and system used
  • Before, during and after photographs
  • Installer and completion date
  • Relevant test or assessment reference